Skip to main content
Skip table of contents

Modbus Reading Expression Syntax

Overview

Modbus register mapping entries allow Modbus register values to be defined using flexible mathematical expressions. This allows for unique registers to be created that acquire data from any monitoring node and process that data to produce the desired reading -- for example to combine power readings from multiple monitoring nodes or to change the measurement units of a certain value.

The expressions can refer to readings from the current node or other nodes. Miscellaneous power-calculation helper functions are also available. For a full set of math functions available see http://mathjs.org/docs/expressions/syntax.html.  

Accessing reading data within mapping expressions

R(channel)

Return reading value on a specific channel

Parameters:

channel: standard data channel name (e.g. VoltageA, CurrentB etc., WITHOUT QUOTES). See the Modbus register map for available channels

Examples:

  • R(VoltageA) - Voltage A reading

  • R(PowerC) - Power C reading

  • R(EnergyA) - Energy A reading

Sample reading channels supported:

(note: specific readings available vary by monitoring node type and configuration and may include channels not listed below - please see specific node documentation for details):

  • VoltageA/B/C

  • CurrentA/B/C

  • PowerA/B/C

  • Power

  • EnergyA/B/C

  • Energy

  • VAA/B/C

  • PhaseAngleA/B/C

  • Temperature0..12

  • Humidity

  • Pressure

R(node, channel)

Return reading value on a specific channel on a specific monitoring node

Parameters:

  • node: node reference, in the formats Nxxxxxxxxxxxxxxxx (x = 16-char hex node ID)

  • channel: standard data channel name (e.g. VoltageA, CurrentB etc., WITHOUT QUOTES)

Examples:

R(NA30000000000AB3E, EnergyA) - Energy A reading of Monitoring node #A30000000000AB3E

JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.