Measurement
|
Temperature |
±0.3°C at 0.1°C resolution; readings available in °C or °F |
|---|---|
|
Temperature probe range |
-20° to 70°C (-4° to 158°F) |
|
Monitor internal temperature range |
0° to 50°C (32° to 122°F) |
|
Relative humidity readings |
0 to 100% RH at ±2% RH at 0.1% resolution |
Communications
|
Operating Frequency |
2.4 GHz (frequencies vary by region) |
|---|---|
|
Wireless Network Protocol |
Frequency hopping self-configuring load-balancing mesh |
|
Data Output |
HTTPS to Packet Power EMX running locally or as cloud service; SNMP V1/V2c/V3; Modbus TCP/IP; EtherNet/IP; |
|
Firmware Updates |
Wireless |
|
Typical Transmission Range |
10 to 30 meters indoors between any two devices in mesh network |
|
Antenna |
Fully enclosed, fixed configuration |
|
Monitoring Unit to Gateway Radio Range |
Up to 25 monitoring units per gateway with battery powered devices |
|
Multi-site Support |
Yes |
|
Encryption |
128-bit encryption (Gateway) |
|
Certifications |
FCC, Industry Canada and CE / IEC |
Environmental & Mechanical
|
Operating Temperature |
0° to 50°C (32° to 122°F) Device size: 56 mm x 40 mm x 19 mm (2.2 in x 1.6 in x 0.75 in) Device weight: 20 g (0.7 oz) Power supply: Lithium coin cell battery Estimated battery life: 4+ years |
|---|---|
|
Operating Humidity |
10% to 90% non-condensing |
|
Water and Dust Resistance |
Indoor use |
|
Module Size |
56 mm x 40 mm x 19 mm (2.2 in x 1.6 in x 0.75 in) |
|
Module Weight |
20 g (0.7 oz) |
|
Power Supply |
Lithium coin cell battery |
|
Estimated Battery Life |
4+ years
|